NOTE: If you are using more than one of these Battery Packs with the
Endeavor 5-10KVA RT series UPS, the UPS must be configured so that the
UPS will report the correct estimated runtime on the LCD screen and in the
Power Monitoring software and/or the SNMP card. See the Power Monitoring
software or the SNMP card’s User's Manual to configure the UPS.
4. Remove both of the External Battery Connector's cover plates from the
rear panel of the first Battery Pack.
5. Remove the top External Battery Connector's cover plate from the rear
panel of the second Battery Pack.
6. Connect the first #8 AWG premolded battery cable to the External Battery
Connector on the rear panel of the UPS and secure with the retaining
screws.
7. Connect the other end of the first #8 AWG premolded battery cable to the
External Battery Connector on the rear panel of the first Battery Pack and
secure with the retaining screws.
8. Connect the second #8 AWG premolded battery cable to the bottom Exte-
rnal Battery Connector on the rear panel of the first Battery Pack and se-
cure with the retaining screws.
9. Connect the other end of the second #8 AWG premolded battery cable to
the top External Battery Connector on the rear panel of the second Battery
Pack and secure with the retaining screws.
10. Turn on all of the DC breakers on the rear panel of the Battery Packs.
11. The Battery Packs are ready for normal operation, see the UPS User's
Manual for the normal startup of the UPS.
NOTE: There is no maximum number for Daisy Chaining the Battery Packs,
however the recharge time will increase exponentially for every Battery Pack
added.
1. The UPS MUST be in the off position.
2. The DC breaker(s) on the rear panel of the Battery Pack(s) MUST be in
the off position.
3. Remove the External Battery Connector's cover plate from the rear panel
of the UPS (requires a phillips screwdriver).
4. Remove the top External Battery Connector's cover plate from the rear
panel of the Battery Pack.
5. Connect the one end of the #8 AWG premolded battery cable to the Exter-
nal Battery Connector on the rear panel of the UPS and secure with the
retaining screws.
6. Connect the other end of the #8 AWG premolded battery cable to the Exte-
rnal Battery Connector on the rear panel of the Battery Pack and secure
with the retaining screws.
7. Turn on the DC breaker on the rear panel of the Battery Pack.
8. The Battery Pack is ready for normal operation, see the UPS User's Manual
for the normal startup of the UPS.
NOTE: If using more than one Battery Pack see Daisy Chaining.
DAISY CHAINING
(QUALIFIED SERVICE PERSONNEL ONLY)
"Daisy Chaining" means connecting one Battery Pack to another Battery Pack
to another Battery Pack, this chain could go on indefinitely. Follow the steps
below to Daisy Chain the Battery Packs. Please read all of the WARNINGS
and CAUTIONS before attempting to connect the external battery pack.
1. The UPS MUST be in the off position.
2. The DC breakers on the rear panel of the Battery Packs MUST be in the
off position.
3. Remove the External Battery Connector's cover plate from the rear panel
of the UPS (requires a phillips screwdriver).