16 Step2 Install the rackmount brackets to the UPS, Isolation Transformer and Battery Pack Step3 Install t
183.5. Wiring the Input and Output Connections (Qualified Electrical Contractor Only) 3.5.1 Connecting the Input and Output wires to the terminal
203.5.2.3.2 Connect the wires from the 208V/240V receptacle box (ED6-208RB) as follows (Output voltage 208V): 1. Connect the Black wire
223.5.2.3.7 Configuration 3. Output: 240VAC 6KVA load and two separate circuits of 120VAC 3KVA loads (3KVA max load per circuit). Total combined outp
243.5.2.3.11 Configuration 7. Output: 208VAC 6KVA load, 240VAC 6KVA load and two separate circuits of 120VAC 3KVA loads (3KVA max load per circuit).
263.5.4 Hardwiring the Input and Output wires to the terminal block on the UPS module when using the UPS without the Isolation Transformer module. C
283.7. Operation and Setup Instructions 3.7.1 Startup in the Normal Mode 3.7.1.1 Switch the Utility power circuit breaker (at the service panel)
303.7.1.7 The UPS has successfully passed the start-up procedure. The UPS will charge the batteries whenever the UPS is connected to an AC source an
32 K * It shows the input frequency from the Bypass Input. L * It shows the Output Voltage from the
34 R1 * It shows the Self-test is “Disabled”. R2 * It shows the Self-test is “Enabled”. S1 *
1Table of Contents 1 Important Safety Instructions...2 1.1 An Important Notic
36 W *It shows the Fine Tune Adjustment % from 0% to 3% or -0% to -3%. X * It shows the UPS Identification Number. Y * It shows t
383.7.6 UPS Is Off Due to Unknown Reason 3.7.6.1 If a serious abnormal condition occurred, the UPS will lock it itself in the “OFF” position as sho
404.2. EPO (Emergency Power Off) Port Connect one end of a two-wire cable to the EPO port and the other end of the two-wire cable to an EPO switch,
426 Troubleshooting Guide If the UPS malfunctions, check the followings: a. Is the wiring of the input and the output correct? b. Is the input volta
447.1. Battery Replacement Procedure (QUALIFIED SERVICE PERSONNEL ONLY) This UPS system has Hot-swappable batteries. Hot-swappable batteries mean th
467.1.14 Gently remove the top part of the plastic battery tray. 7.1.15 Disconnect the red battery wire from the battery terminal. 7.1.16 Disconne
48 BATTERY (The batteries are in the Battery Pack ONLY. The UPS module does NOT have internal batteries.) Type Sealed, Non-Spillable, Maintenance Fr
5010 Limited Product Warranty Para Systems, Inc. (Para Systems) warrants this equipment, when properly applied and operated within specified conditi
21 Important Safety Instruction 1.1. An Important Notice 1.1.1 To ensure safety in all applications where a UPS system is hardwired to the elect
42 Product Introduction 2.1. System Overview This On-Line UPS protects computers, servers, internetworking, and telecommunications equipment from
6 11 LINE OFF UPS Abnormal Lock 12 UPS Flow Chart 13 4 Digits Measurement Display 14 Indicate the item desired to be measured 15 ON a
8 46 Er22 Bypass SCR or Output Fuse Fails 47 Er23 Inverter Relay or SCR or Output Fuse Fails 48 Er24 Bypass found when running on CVCF mode 49 Er26 P
10 On/Alarm Silencer switch is to turn the UPS On or silence the audible alarm in the Battery mode. OFF switch is to turn the inverter Off and tra
123 Installation and Operation (QUALIFIED SERVICE PERSONNEL ONLY) Be sure to read the Installation Placement and all of the CAUTIONS and the WARNIN
143.4. Installation of the Caster Covers (QUALIFIED SERVICE PERSONNEL ONLY) 3.4.1 Tower Installation 3.4.1.1 UPS and Battery Pack (only)